Johnson Pump logo

Parameter settings for Danfoss VLT® 6000 HVAC
Local Control Panel

0/4 - 20 mA signal from controller

Local Control Panel for VLT 6000 HVAC

Click on the Control Panel for more info.

 

The parameters used to control the frequency converters may be easily programmed by the user. The [QUICK MENU] button provides a list with a some of the most common parameters. The [EXTEND. MENU] button allows the user to program all parameters.

Johnson Pump Horticulture provides you with this Quick Start guide for optimizing your pump performance.

This guide assumes you are using the Display in Display mode II.

     
Parameter settings    
Group 0 - Operation & Display    
Param. no. Description Window text Setting Serial port value
001 Language LANGUAGE ENGLISH 0
007 Large display readout LARGE READOUT FREQUENCY [Hz] 3
008 Small display readout 1.1 SMALL READOUT 1 POWER [KW] / [HP] 6 / 7
009 Small display readout 1.2 SMALL READOUT 2 MOTOR CURRENT [A] 5
010 Small display readout 1.3 SMALL READOUT 3 ANALOG INPUT 60 [mA] 23
         
Group 1 - Load & Motor    
Param. no. Description Window text Setting Serial port value
100 Configuration CONFIG. MODE OPEN LOOP 0
         
Group 2 - References & Limits    
Param. no. Description Window text Setting Serial port value
201 Output frequency low limit, fMIN MIN. FREQUENCY 0.000 Hz 0
202 Output frequency high limit, fMAX MAX. FREQUENCY 50.000 Hz 500
204 Minimum reference, RefMIN MIN. REFERENCE 0.000 HZ 0
205 Maximum reference, RefMAX MAX. REFERENCE 50.000 Hz 50000
206 Ramp-up time 1 RAMP UP TIME 1 15.00 sec. 15
207 Ramp-down time RAMP DOWN TIME 1 15.00 sec. 15
         
Group 3 - Inputs & Outputs    
Param. no. Description Window text Setting Serial port value
308 Terminal 53, analogue input voltage AI [V] 53 FUNCT. NO OPERATION 0
314 Terminal 60, analogue input current AI [mA] 60 FUNCT. REFERENCE 1
315 Terminal 60, min. scaling AI 60 SCALE LOW 0.0 or 4.0 mA 0 or 40000
316 Terminal 60, max. scaling AI 60 SCALE HIGH 20 mA 200000
         
All other parameter settings --> factory default setttings
back to top
 

Troubleshooting
Not working?
Parameter 620 [OPERATION MODE]/[INITIALIZE] can be used to rest all parameters to the default factory settings.
Procedure for intitialisation:

  1. Select initialisation (parameter 620)
  2. Press [OK]
  3. Disconnect mains power supply and wait for the light in the display to go out
  4. Reconnect to mains
  5. Initialisation of alll parameters will be carried out
  6. Reprogram the above parameters
back to top
 
Wiring diagram
wiring diagram for VLT6000 0/4-20mA signal

The connection between terminal 12 and 18 can be replaced by a contact from the controller.

Press [DISPLAY MODE].
Three values are shown at the top of the display; parameter settings 008, 009 and 010.
The value on the far right is the voltage connected to terminal 60.

back to top
 