Parameter settings for Danfoss VLT® 6000 HVAC 4 - 20 mA signal from pressure transmitter | |||
| Click on the Control Panel for more info. | The parameters used to control the frequency converters may be easily programmed by the user. The [QUICK MENU] button provides a list with a some of the most common parameters. The [EXTEND. MENU] button allows the user to program all parameters. | |||
| Parameter settings | ||||
| Group 0 - Operation & Display | ||||
| Param. no. | Description | Window text | Setting | Serial port value |
| 001 | Language | LANGUAGE | ENGLISH | 0 |
| 005 | Max. value of user-defined readout | CUSTOM READOUT | 600.00 | 60000 |
| 006 | Unit for user-defined readout | CUST. READ. UNIT | mbar | 15 |
| 007 | Large display readout | LARGE READOUT | FREQUENCY [Hz] | 3 |
| 008 | Small display readout 1.1 | SMALL READOUT 1 | SET POINT 1 [UNITS] | 11 |
| 009 | Small display readout 1.2 | SMALL READOUT 2 | FEEDBACK 1 [UNITS] | 13 |
| 010 | Small display readout 1.3 | SMALL READOUT 3 | ANALOG INPUT 60 [mA] | 23 |
| Group 1 - Load & Motor | ||||
| Param. no. | Description | Window text | Setting | Serial port value |
| 100 | Configuration | CONFIG. MODE | CLOSED LOOP | 1 |
| Group 2 - References & Limits | ||||
| Param. no. | Description | Window text | Setting | Serial port value |
| 201 | Output frequency low limit, fMIN | MIN. FREQUENCY | 0.000 Hz | 0 |
| 202 | Output frequency high limit, fMAX | MAX. FREQUENCY | 50.000 Hz | 500 |
| 204 | Minimum reference, RefMIN | MIN. REFERENCE | 0.000 | 0 |
| 205 | Maximum reference, RefMAX | MAX. REFERENCE | 600.000 | 600000 |
| 206 | Ramp-up time 1 | RAMP UP TIME 1 | 15.00 sec. | 15 |
| 207 | Ramp-down time | RAMP DOWN TIME 1 | 15.00 sec. | 15 |
| Group 3 - Inputs & Outputs | ||||
| Param. no. | Description | Window text | Setting | Serial port value |
| 308 | Terminal 53, analogue input voltage | AI [V] 53 FUNCT. | NO OPERATION | 0 |
| 314 | Terminal 60, analogue input current | AI [mA] 60 FUNCT. | FEEDBACK | 2 |
| 315 | Terminal 60, min. scaling | AI 60 SCALE LOW | 4.0 mA | 40000 |
| 316 | Terminal 60, max. scaling | AI 60 SCALE HIGH | 20.0 mA | 200000 |
| Group 4 - Special functions | ||||
| Param. no. | Description | Window text | Setting | Serial port value |
| 413 | Minimum Feeback, FBMIN | MIN. FEEDBACK | 0.000 | 0 |
| 414 | Maximum feedback, FBMAX | MAX. FEEDBACK | 600.000 | 600000 |
| 415 | Units relating to closed loop | REF. / FDBK. UNIT | mbar | 15 |
| 418 | Setpoint 1 | SETPOINT 1 | 100.000 | 100000 |
| 423 | PID proportional gain | PID PROP. GAIN | 1.00 | 100 |
| 424 | PID integration time | PID INTERG. TIME | 10.00 sec. | 1000 |
| All other parameter settings --> factory default setttings | ||||
Troubleshooting
|
| Wiring diagram |
![]() |
The pressuretransmitter must be connected as showed in the diagram. The connection between terminal 12 and 18 can be replaced by a contact from the controller.
When the transmitter is connected correctly, press [AUTO START].
|
| PDF downloads |
6000 HVAC Quick Guide 4-20 mA pressure signal (112 kB PDF) 6000 HVAC button functions, Display modes and general programming (136 kB PDF) |