Parameter settings for Danfoss VLT® 6000 HVAC
Local Control Panel

4 - 20 mA signal from pressure transmitter

Local Control Panel for VLT6000 HVAC

Click on the Control Panel for more info.

 

The parameters used to control the frequency converters may be easily programmed by the user. The [QUICK MENU] button provides a list with a some of the most common parameters. The [EXTEND. MENU] button allows the user to program all parameters.

Johnson Pump Horticulture provides you with this Quick Start guide for optimizing your pump performance.

This guide assumes you are using the Display in Display mode II.

     
Parameter settings    
Group 0 - Operation & Display    
Param. no. Description Window text Setting Serial port value
001 Language LANGUAGE ENGLISH 0
005 Max. value of user-defined readout CUSTOM READOUT 600.00 60000
006 Unit for user-defined readout CUST. READ. UNIT mbar 15
007 Large display readout LARGE READOUT FREQUENCY [Hz] 3
008 Small display readout 1.1 SMALL READOUT 1 SET POINT 1 [UNITS] 11
009 Small display readout 1.2 SMALL READOUT 2 FEEDBACK 1 [UNITS] 13
010 Small display readout 1.3 SMALL READOUT 3 ANALOG INPUT 60 [mA] 23
         
Group 1 - Load & Motor    
Param. no. Description Window text Setting Serial port value
100 Configuration CONFIG. MODE CLOSED LOOP 1
         
Group 2 - References & Limits    
Param. no. Description Window text Setting Serial port value
201 Output frequency low limit, fMIN MIN. FREQUENCY 0.000 Hz 0
202 Output frequency high limit, fMAX MAX. FREQUENCY 50.000 Hz 500
204 Minimum reference, RefMIN MIN. REFERENCE 0.000 0
205 Maximum reference, RefMAX MAX. REFERENCE 600.000 600000
206 Ramp-up time 1 RAMP UP TIME 1 15.00 sec. 15
207 Ramp-down time RAMP DOWN TIME 1 15.00 sec. 15
         
Group 3 - Inputs & Outputs    
Param. no. Description Window text Setting Serial port value
308 Terminal 53, analogue input voltage AI [V] 53 FUNCT. NO OPERATION 0
314 Terminal 60, analogue input current AI [mA] 60 FUNCT. FEEDBACK 2
315 Terminal 60, min. scaling AI 60 SCALE LOW 4.0 mA 40000
316 Terminal 60, max. scaling AI 60 SCALE HIGH 20.0 mA 200000
         
Group 4 - Special functions    
Param. no. Description Window text Setting Serial port value
413 Minimum Feeback, FBMIN MIN. FEEDBACK 0.000 0
414 Maximum feedback, FBMAX MAX. FEEDBACK 600.000 600000
415 Units relating to closed loop REF. / FDBK. UNIT mbar 15
418 Setpoint 1 SETPOINT 1 100.000 100000
423 PID proportional gain PID PROP. GAIN 1.00 100
424 PID integration time PID INTERG. TIME 10.00 sec. 1000
         
All other parameter settings --> factory default setttings
back to top
 

Troubleshooting
Not working?
Parameter 620 [OPERATION MODE]/[INITIALIZE] can be used to rest all parameters to the default factory settings.
Procedure for intitialisation:

  1. Select initialisation (parameter 620)
  2. Press [OK]
  3. Disconnect mains power supply and wait for the light in the display to go out
  4. Reconnect to mains
  5. Initialisation of alll parameters will be carried out
  6. Reprogram the above parameters
back to top
 
Wiring diagram
wiring diagram for VLT6000 4-20mA pressure signal

The pressuretransmitter must be connected as showed in the diagram.

The connection between terminal 12 and 18 can be replaced by a contact from the controller.

Attention!
P1 of the transmitter is connected to the Supply.
P2 of the transmitter has to be connected to the Return.


To check if the transmitter is connected correctly:

  1. Press [DISPLAY MODE]
  2. Three values are shown in the display; parameter settings 008, 009 and 010.
  3. The value to the right must be 3,8/3,9 mA while the pump is not running. When this value is 0 mA while the pump is not running, the transmitter is connected wrong or the parameter setting 315 is on 0 mA. When the value is 21 mA while the pump is not running, the pressure difference is more then 600 mbar or the transmitter is not working.

When the transmitter is connected correctly, press [AUTO START].

  1. The pump wil run and the value to the right will increase till 6,5 mA (100 mbar).
  2. The value in the middle will swing around 100 mbar (measured value transmitter).
  3. The value to the left will be 100 (PRESET REF 418 ).